What thermostat can I connect ?
- The electric boiler can accept any type of dry contact room thermostat (also known as potential-free or On/Off contact), provided that it is not of the "chrono-proportional" type.
- Auer offers 3 thermostat models (TA - Room thermostat ref. 710043, TH Room thermostat with clock ref. 710044, and TH RNC Wireless room thermostat non-chrono-proportional ref. 710172)
- It connects to the boiler with 2 wires on terminals 1 and 2. If there is no room thermostat, no bridging is required.
- It can be wireless with radio frequency transmission.
- It can incorporate a clock. To be recognized by the electric boiler, simply set the control (parameter No. 04 = 01).
Ces questions peuvent aussi vous intéresser
Comment régler la vitesse du circulateur ?Réaliser un délestage partiel ou total de la chaudière ?Peut-on abaisser la puissance de Gialix ?Que faut-il faire pour installer la production d’ECS ?Utiliser le signal heures creuses / heures pleinesComment piloter la chaudière par un régulateur externe ?How to connect and declare a room thermostat ?Raccorder et déclarer une sonde extérieure en AUTOComment accéder aux paramètres installateur ?Informations et consigne de chauffage calculée par chaudièreComment programmer des plages horaires ?