How to connect and declare a room thermostat ?
Connect the room thermostat to terminals 1 and 2 of the boiler.
Use parameter 04 to declare a thermostat
- In the parameter setting menu, set parameter 04 to value 01: presence of a room thermostat.
Activatable option: Circulator control based on thermostat demand
- In the parameter setting menu, set parameter 05 to value 01: circulator control based on thermostat demand.