Use off-peak / peak hours signal.
Connect the off-peak signal output to terminals 7 and 8 of the boiler.
- The output must be converted into a dry contact, operated according to the logic:
- closed contact = off-peak hours - normal boiler operation
- open contact = peak hours - boiler operation limitation
Use parameter 23 to choose the level of reduction.
- In the parameter setting menu, set parameter 23 to the value:
- 01: ECO setting during peak hours
- 02: FROST setting during peak hours
These questions might also interest you
How to adjust the speed of the circulator?Performing a partial or total shedding of the boiler ?Can the power of Gialix be reduced ?What needs to be done to install the domestic hot water production ?How to control the boiler with an external controller ?How to connect and declare a room thermostat ?Connect and declare an outdoor sensor in AUTO modeHow to access the installer settings ?Information and heating setpoint calculated by boilerHow to program time slots ?What thermostat can I connect ?